Troubleshooting

Device Offline

Rubix CE can detect if a device is offline. To check the availability of the device, navigate to the Host View. max800px
Click update-status-button.png to update the current online/offline status of the devices.

Device Offline for Remote Connections

Network Downtime: Network signal is poor or nonexistent, the on-site engineer is advised to take the following steps to ensure connectivity:

  • Check on the router's reception indicator.
  • Restart the problematic device or check if the router is working correctly.
  • Inspect the SIM integrity.

Device Offline for Local Network without Internet

  • Ensure the device is powered on.
  • Verify the network configuration is correct.
  • Check for any damage to the Ethernet cable.
  • Verify if other devices on the same network are experiencing similar issues.
  • Restart the router to refresh the network connection.

System Performace

If Rubix CE experiences performance issues, you can diagnose potential causes by accessing system information in the Info section under settings. This information includes CPU usage, memory usage, swap memory usage, and disk usage. analysing these metrics can help pinpoint the source of performance degradation and guide troubleshooting efforts to address the underlying issues.

max800px

Rubix Host/Supervisor Level Troubleshooting

  • Initiate a ping to the Host/Supervisor by right-clicking on it as shown in the image below: max800px
  • After confirming connectivity with the host/supervisor, authenticate by right-clicking and selecting Login.
  • Once logged in, verify the presence of Rubix-OS. If it is not installed, you can install it by right-clicking on Rubix-OS and selecting Install.
  • Additionally, for troubleshooting purposes, you can restart Rubix-OS from the right-click menu, which can resolve issues on problematic systems. Restarting Rubix-OS can help resolve various issues by resetting its state and clearing temporary glitches or errors that may have occurred during operation.

Network/Device/Points Level Troubleshooting

  • If a network/device/points is highlighted in orange, scroll right to identify potential issues. See Error Lists below for more information.
  • In this example, the error message indicates either the plugin is not enabled or there's no valid message from the network. max800px
  • You will need to confirm that the module is installed correctly, the app is enabled, and functioning properly. For instructions on navigating through apps and modules, please refer to modules and apps respectively. max800px
  • In the image above, observe that BacNet is currently activating. This can be the reason why the plugin is is highlighted in orange.
  • Restart the driver to refresh the connection. See if problem still persists.
  • Sometimes, even if the plugin is enabled, errors persist due to incorrect parameters. Ensure that the parameters configured in your driver match those of the devices you're attempting to connect to. You can edit the these parameters at the drivers tab. See drivers and select the driver you wanted to explore.

Error Lists

ModuleLevelMessageIssue
module-core-bacnetDevicesNo response from target devicewhen driver-bacnet app doesn't get a response from the target device (timeout)
module-core-bacnetPointsunknown-objectif the mapped point doesn't exist in the bacnet-server
module-core-bacnetPointstimed outno value received from driver-bacnet app polling
module-core-modbus (Serial)Networkcould not open <serial_port>: no such file or directorywhen there is no such serial port available
module-core-modbus (Serial)Devicesserial: timeoutwhen the poll point gets timeout (normally it happens if there's a connection issue)
module-core-modbus (Serial)Devicescould not open <serial_port>: no such file or directorywhen there is no such serial port available
module-core-modbus (Serial)Pointsserial: timeoutwhen the poll point gets timeout (normally it happens if there's a physical connection issue)
module-core-modbus (Serial)Pointscould not open <serial_port>: no such file or directorywhen there is no such serial port available
module-core-modbus (TCP)Devicesdial tcp <ip>:<port>: connect: connection refusedconnection refuse, check IP & port
module-core-modbus (TCP)Devicesdial tcp <ip>:<port>: i/o timeoutwhen the poll gets timeout (normally it happens if there's a physical connection issue)
module-core-modbus (TCP)Pointsdial tcp <ip>:<port>: i/o timeoutwhen the poll point gets timeout (normally it happens if there's a physical connection issue)